Connectors & fibre types

Đội ngũ của chúng tôi đang thực hiện bản dịch. Bài viết này tạm thời chưa có bản tiếng Việt và đang được hiển thị bằng tiếng Anh.

The module is only half of a link; the other half is the glass and the connector that mates to it. Mismatched fibre or polish costs decibels silently, and a dirty ferrule is the single most common cause of a "bad module". This page is the field reference.

Fibre types

TypeCore / claddingJacket colourBandwidth (850 nm)Typical reachUsed with
OM162.5 / 125 µmorange200 MHz·km1G 275 m; 10G 33 mlegacy campus
OM250 / 125 µmorange500 MHz·km1G 550 m; 10G 82 mlegacy
OM350 / 125 µmaqua2 000 MHz·km10G 300 m; 40/100G SR4 100 mdata centre
OM450 / 125 µmaqua / violet (Erika)4 700 MHz·km10G 400 m; 100G SR4 100–150 mdata centre standard
OM550 / 125 µmlime greenwideband 850–953 nmas OM4 + SWDM4multi-wavelength MMF
OS1 / OS29 / 125 µmyellow10 km … 80 km+all single-mode optics

Single-mode subtypes: G.652.D (standard, low water peak — the default), G.657 (bend-insensitive, for tight indoor routing), G.655 (non-zero dispersion-shifted, legacy DWDM plant), G.654 (low-loss, submarine/long-haul).

Rules: never mix 50 and 62.5 µm multi-mode on one link (up to 4 dB loss at the joint); never plug a multi-mode module into single-mode fibre or vice versa — the link may come up marginally and fail later. Multi-mode reach is set by modal bandwidth, not attenuation; single-mode reach by attenuation and dispersion (Wavelength bands).

Connectors

ConnectorFerruleWhere
LC1.25 mm, duplex or simplexthe standard on SFP/SFP+/SFP28, QSFP LR4/FR4, 400G FR4
SC2.5 mm, push-pullGBIC, PON (SC/APC), patch panels, older plant
FC2.5 mm, screw-ontest equipment, legacy telecom
ST2.5 mm, bayonetlegacy multi-mode
E20002.5 mm with shutterEuropean telecom, APC
MPO / MTP12/16/24-fibre arraySR4/SR8/DR4/DR8/PSM4 parallel optics; MTP is a premium MPO variant
SN / CSdual 1.25 mm, very small400G/800G breakout (2×LC in one QSFP-DD faceplate)
MDCdual 1.25 mm, very smallhigh-density 400G/800G
MU1.25 mmlegacy telecom

Polish: UPC vs APC

PolishEnd-faceBoot colourReturn lossUse
PC / UPCflat / ultra-polished, 0°blue (SMF), beige/black (MMF)≥ 50 dBEthernet, FC, data centre
APCangled 8°green≥ 60 dBPON, DWDM, analogue video, 400G DR4/800G DR8 MPO

Never mate UPC to APC — the angled and flat faces cannot touch; expect several dB of loss and possible end-face damage. High-speed single-mode MPO (DR4/DR8) is APC, and InfiniBand NDR insists on it (InfiniBand optics).

MPO essentials

  • Pinned vs unpinned — a pinned (male) connector mates only with an unpinned (female); transceivers are usually pinned, so patch cords are female–female.
  • Fibre count — MPO-12 for SR4/DR4 (8 fibres used), MPO-16 for SR8/DR8, MPO-24 for legacy SR10.
  • Polarity — Type A (straight), B (reversed), C (pair-flipped) cabling; a wrong polarity mix gives Tx-to-Tx and no link. Standardise on one method per site.
  • Key up / key down and APC angle orientation matter — follow the labels.

Cleaning and inspection

One 2–5 µm particle adds 0.5–2 dB; a clean LC pair costs 0.1–0.2 dB. Inspect → clean → re-inspect, dry cleaning after wet; one-click cleaners for LC/SC, dedicated MPO cleaners for arrays. Details and the diagnostic ladder: Link flapping, CRC & dirty connectors.

Cables with fixed ends

DAC (copper) and AOC (active optical) cables carry module ends permanently attached — no connector to clean, but nothing to replace except the whole cable (DAC vs AOC, Copper & DAC).

What the module memory says

The connector type is a byte in the identity block (SFF-8472 A0h byte 2, SFF-8636 byte 130), coded per SFF-8024: 07h = LC, 01h = SC, 0Ch = MPO 1×12, 0Dh = MPO 2×16, 21h/22h = copper pigtail/RJ45, 23h = no separable connector (AOC/DAC). Length fields (bytes 14–19) declare the fibre types the module is rated for. CodingBox decodes both on the Check transceiver screen; see the Memory map quick reference.

What goes wrong when fibre, polish or polarity do not match — and how it shows up — is in Physical-layer mismatches.

How MPO connectors are used in structured cabling — polarity methods, trunks and cassettes, Base-8 vs Base-12: Breakout & MPO cabling.

Full reach matrix per PMD × OM1–OM5/OS2, plus FC, InfiniBand, PON and cable lengths: Reach tables; latch, jacket and boot colour codes in one place: Labels & colour codes.

The physics behind these grades — modes, numerical aperture, mode field diameter, bend loss: How light propagates in fibre; the rest of the passive plant these connectors live in — cables, panels, pigtails, splices, splitters, filters: Passive plant.

The standards behind the fibre column — ITU-T G.652–G.657, IEC multi-mode codes, specialty fibres and dissimilar-fibre joints: Fibre types; eye safety around live connectors and the handling rules for modules and cords: Safety and handling.

Endface grading against IEC 61300-3-35 — zones A–D, allowed scratches and defects per connector type, contamination types and cleaning methods including MPO and transceiver receptacles: Endface inspection & cleaning.