CodingBox Documentation

Testing and measurement: LSPM, OTDR, return loss, inspection

A fibre link is accepted, certified and later diagnosed with a small set of instruments: a light source and power meter for the total loss, an OTDR for the loss of each event along the route, a return-loss meter for reflections, and a microscope for the connector endfaces that cause most trouble. The transceiver's own DDM is a fifth instrument, always present. This page explains what each measures, how to use it correctly (reference methods, launch cords, wavelengths), how to read an OTDR trace, what the certification standards require, and where DDM fits.

The instruments

InstrumentMeasuresAccuracyUse
Light source + power meter (LSPM / OLTS)insertion loss of the whole link, end to end, at 850/1300 (MMF) or 1310/1550/1625 (SMF)±0.1–0.2 dBacceptance (Tier 1), troubleshooting total loss
OTDR (optical time-domain reflectometer)loss and reflectance of each event (connector, splice, bend, break) versus distance; fibre attenuation per km±0.05 dB per event, ±1 m distance (after calibration of refractive index)characterisation (Tier 2), fault location
Return-loss meter / OCWRtotal back-reflection of the link±0.5 dBUPC vs APC verification, laser stability
Fibre inspection microscopeendface scratches, pits, contaminationper IEC 61300-3-35 zonesbefore every mating
Visual fault locator (VFL)red laser (650 nm) visible through jacket at breaks and tight bendstracing, gross faults, polarity
Fibre identifierlive traffic direction and presence by bendingbefore disconnecting the wrong fibre
Optical spectrum analyser (OSA)wavelengths, channel powers, OSNRWDM (OSNR)
Transceiver DDMTx and Rx power at the link ends±3 dB spec, ±1 dB typicalin-service monitoring (Reading DDM with tools)

Insertion loss with LSPM (Tier 1)

  1. Reference: connect source and meter with the test reference cords and zero the meter (0 dB). The one-jumper reference (TIA-526-14/ISO 14763-3 method A) includes both link connectors in the result; the two- or three-jumper methods exclude one or both.
  2. Measure: insert the link under test between the reference cords; read the loss at each wavelength, both directions if required (IEC recommends bidirectional).
  3. Compare with the design budget and the standard's pass value: link loss ≤ (fibre length × coefficient + connector pairs × allowance + splices × allowance).
  4. Wavelengths: MMF at 850 and 1300 nm; SMF at 1310 and 1550 nm (1625 nm to reveal bends). Multi-mode sources must have the standard encircled flux launch.
PitfallEffect
Dirty reference cord0.5–2 dB error on every link
Reference cord of a different grade or MFDoffset of 0.1–0.5 dB
Wrong reference method for the standardlink connectors counted twice or not at all
Laser source into multi-mode without encircled flux compliancereads too low or too high by up to 1 dB
Measuring only one wavelengthmisses bends (1550/1625) or water-peak issues

OTDR (Tier 2)

The OTDR sends pulses and times the backscatter; loss appears as a drop in the trace, reflections as spikes.

Trace featureMeaning
Steady slopefibre attenuation (dB/km) — should match the cable spec
Step down without spikefusion splice or bend (non-reflective event)
Spike then step downconnector or mechanical splice (reflective event)
Spike to the top, then noiseend of fibre or break; open connector
Step up (gainer)splice between fibres of different backscatter (MFD); average both directions
Spike without step, far awayghost — multiple reflection; not a real event
Rising slope near endhigh-reflectance end saturating the receiver
SettingGuidance
Pulse widthshort (5–30 ns) for close events and resolution; long (1–10 µs) for range; dead zones grow with pulse width
Range1.5–2 × fibre length
Averaging30–180 s for splice-level accuracy
Refractive indexfrom the cable datasheet (1.467–1.470 for G.652); a 0.001 error = 0.07 % distance
Launch and receive cords300–1 000 m (SMF) / 100–300 m (MMF) so the first and last connectors sit outside the dead zone
Wavelengths1310 + 1550 (SMF), 1625 for bend hunting; 850 + 1300 (MMF)
Bidirectional testrequired for accurate splice loss (averages the MFD artefact)

Event dead zone 1–3 m, attenuation dead zone 5–20 m: two events closer than that merge.

Return loss and reflectance

QuantityDefinitionGood values
Reflectance of one eventreflected/incident power at that event, dB (negative)UPC connector −50 dB or better; APC −65; splice < −70
Optical return loss (ORL) of a linktotal reflected power, dB (positive)> 27 dB (10G), > 35 dB (analog video, DWDM); > 45 dB APC links

Reflections destabilise DFB lasers and add interferometric noise; standards specify minimum ORL for the PMD (e.g. 12 dB for 10GBASE-LR, 21 dB for 1000BASE-LX — the module's own tolerance; plant design aims far higher).

Endface inspection (IEC 61300-3-35)

ZoneDiameter (SMF)Allowed
A — core0–25 µmno scratches, no defects
B — cladding25–115 µmno defects > 2 µm (a few ≤ 2), no scratches > 3 µm
C — adhesive115–130 µmnot assessed
D — contact130–250 µmno defects > 10 µm

Inspect both sides of every mating (the adapter side with a probe tip); clean with a one-click cleaner or lint-free wipe and re-inspect. Automated pass/fail scopes apply the zones (Connectors & fibre).

Certification and documentation

StandardTier 1 (loss)Tier 2 (OTDR)Notes
ANSI/TIA-568.3-D + TIA-526-7/14requiredoptional/recommendedloss budget = attenuation coefficient × length + 0.75 × pairs + 0.3 × splices
ISO/IEC 14763-3requiredrecommendedgrade-based connector allowances
IEC 61280-4-1 / -4-2MMF / SMF test methodsencircled flux for MMF
Customer / carrier acceptanceloss per fibre at 2 wavelengths, bidirectional OTDR traces, ORL, endface imagesdelivered as a test report per fibre

Keep the reports: the difference between installed loss and today's loss is the first question in any later fault (Plant faults).

Using DDM as a meter

The transceiver reports Tx power at one end and Rx power at the other; the difference is the link loss — within DDM accuracy (±3 dB by spec, ±1 dB on good modules, better after comparing to a real meter once).

UseHow
Sanity check of a new linkexpected Rx = Tx − design loss; ±2 dB deviation → measure with LSPM
Trend monitoringlog Rx power; a slow 1 dB decline = connector contamination or bend; sudden 3 dB = event (Monitoring)
Which end is badcompare both directions: asymmetric loss points to a directional fault (bad connector on one Tx side)
Calibrationmeasure one link with a meter and note the DDM offset (Calibration)

In CodingBox

Bench measurement of the module itself — Tx power into a short reference cord, Rx power from a calibrated source — separates a weak module from a lossy plant before the OTDR comes out. CodingBox reads the module's DDM and thresholds and lets you record the values against the serial number (DDM in the app, Accuracy & limits).

What the OTDR is judging — the splicing process, its acceptance limits and the defects behind a bad event: Splicing and termination; these measurements as part of the maintenance cycle, baselines and restoration: Maintenance and restoration.