Fibre link loss calculator for acceptance testing — CodingBox

All tools

Link loss for acceptance

Work out the loss limit of an installed link at both test wavelengths from its length, connections and splices, and check a light source and power meter reading against it.

Standard and fibre
Link
Count both ends of the link.
Splitters, mux and demux, filters in the path.
Allowances
Measured loss (optional)

Loss limit

Item1310 nm1550 nm
Fibre——
Connectors——
Splices——
Other——
Loss limit, dB——
Measured — —

All values in dB. The limit is the most a compliant link may lose; a well-built link measures well below it.

How the limit is calculated

Loss limit = attenuation coefficient × length + connector pairs × loss per pair + splices × loss per splice + other components, separately at each test wavelength: 1310 and 1550 nm for single-mode, 850 and 1300 nm for multimode.

AllowanceTIA-568.3-DDesign allowances
Connector pair0.75 dB0.5 dB
Splice0.3 dB0.1 dB
Single-mode fibre, 1310 / 1550 nm0.5 / 0.5 dB/km0.35 / 0.22 dB/km
Multimode fibre, 850 / 1300 nm3.0 / 1.5 dB/km3.0 / 1.0 dB/km

A standard gives the most a compliant link may lose; a well-built link measures well below it. ISO/IEC 14763-3 grades connections and customer or carrier specifications are often stricter — enter their allowances as custom values, use the stricter set and record which one you used.

Measure insertion loss with a light source and a power meter at both working wavelengths. With a one-jumper reference the result includes the connections at both ends of the link — count them as connector pairs; the two- and three-jumper methods leave one or both of them out. Investigate any connection above 0.5 dB, even when the link as a whole passes.

More in the documentation: Testing and measurement, Link budget engineering, Typical values.